From: Richard Palluzi <000006c59248530b-dmarc-request**At_Symbol_Here**LISTS.PRINCETON.EDU>
Subject: Re: [DCHAS-L] Pressurization of 5 gallon glass carboy
Date: Fri, 25 Feb 2022 08:33:17 -0500
Reply-To: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**Princeton.EDU>
Message-ID: 005c01d82a4c$3fd58ab0$bf80a010$**At_Symbol_Here**verizon.net
In-Reply-To


I am forced to argue that relying on stoppers or corks popping off or tubing
blowing off as a pressure reliving mechanism is not a method allowed by any
fire or safety code. Worse, I have seen too many cases where the cork,
stopper, or tubing was in so tightly that if failed to release and created a
failure in the glassware. I strongly encourage everyone to help spread the
word that this type of "safety" precaution is neither safe nor effective
before another accident occurs.

Richard Palluzi
BE(ChE), ME(ChE), PE, CSP,FAIChE

Pilot plant and laboratory consulting, safety, design, reviews, and training
www.linkedin.com/in/richardppalluzillc/

Richard P Palluzi LLC
72 Summit Drive
Basking Ridge, NJ 07920
rpalluzi**At_Symbol_Here**verizon.net
908-285-3782

-----Original Message-----
From: ACS Division of Chemical Health and Safety On
Behalf Of Stephen Stepenuck
Sent: Friday, February 25, 2022 2:02 AM
To: DCHAS-L**At_Symbol_Here**Princeton.EDU
Subject: Re: [DCHAS-L] Pressurization of 5 gallon glass carboy

A dissenting voice if I may:
If the apparatus involved was inherited in a PChem lab, as
described, it sounds to me like the carboy [or carboys] was probably used
for the Clement-De´sormes Experiment for determining the Ratio of the heat
capacities of gases. I always thought that this had to be one of the most
ingenious experiments in the history of science?so simple, yet yielding
thermodynamic data. I don1t remember the exact specs, but I1ll bet that1s
what the carboy was for. With a bit of luck you might find a manometer in
the lab filled not with Hg, but with an organic liquid, maybe dioctyl
phthalate or some such. I suspect the carboy [or perhaps in a drawer in the
lab] was equipped with a large rubber stopper and three short glass tubes
though the stopper.
Anyway, safety wise: I can1t remember the specs here either, but I
would guess that one pressurizes the gas in the carboy to maybe 10cm of the
low-vp organic liquid, then waits for thermal equilibrium. Once there, the
manometer is read, and the small rubber stopper at the neck is quickly
removed and replaced. That causes an adiabatic expansion of the gas, which
cools it. Then one waits again for heat to flow through the walls, and
reads the manometer a final time. The pressures now reflect an isothermal
expansion interval.
The pressure is increased by using a small hand bulb with a check
valve?not much pressure at all, plus you have pressure relief from the
rubber stoppers and vinyl or rubber tubing. For the Clement-De´sormes
experiment, it is convenient to keep a separate carboy for each gas studied,
which could account for more than one carboy1s having been found.
I1ve had students do this experiment many times [having always been
in very low-budget situations] and don1t wee a problem.
Of course if that1s not what these were for, it1s a new ball game.
If those were used for the ignition of an organic vapor a la Hubert
Alyea et al., if done the carboys should be thoroughly taped and secured
behind appropriate shields. Polycarbonate carboys have been used for that
one, which I never dared to do.

Good luck,
Steve

--
Stephen J. Stepenuck, Ph.D.
Emeritus professor of chemistry
Keene State College
Keene NH 03435-2001
sstepenuck**At_Symbol_Here**ne.rr.com
603.352.7540


Ralph wrote:

>One of our faculty member was doing due diligence inspections on
>inherited equipment he uses in the physical chemistry lab for gas
>demonstrations. He found some defects in glass 5 gallon carboys, so
>ordered replacements. They arrived from DWK-Kimble with precautions
>etched on the outside, including 3Do not evacuate or pressurize unless
>recommended in the current DWK Kimble catalog.2 Unfortunately, the
>catalog does not contain any information about pressurizing or evacuating
>the carboys. It simply says that the carboys are "Ideal for storage and
>dispensing of solutions.2
>
>There are no discernible design differences between the new carboys and
>the older ones. I wonder if anyone on the list has experience with
>assessing the risk associated with gas pressure differences with this
>equipment?
>
>Thanks for any information on this.
>
>- Ralph
>
>
>Ralph Stuart, CIH, CCHO
>Environmental Safety Manager
>Keene State College
>603 358-2859
>
>ralph.stuart**At_Symbol_Here**keene.edu
>
>---
>For more information about the DCHAS-L e-mail list, contact the
>Divisional membership chair at membership**At_Symbol_Here**dchas.org
>Follow us on Twitter **At_Symbol_Here**acsdchas

---
For more information about the DCHAS-L e-mail list, contact the Divisional
membership chair at membership**At_Symbol_Here**dchas.org
Follow us on Twitter **At_Symbol_Here**acsdchas

---
For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org
Follow us on Twitter **At_Symbol_Here**acsdchas

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.