Larry,
Our local ordinance for secondary containment for hazardous material
storage (which would include haz waste) states:
1. The containment material is compatible with the stored material
(it won't be degraded by a spill).
2. All materials stored in the same secondary containment are
compatible (they won't chemically react with each other).
3. The volume of the secondary containment needs to be 110% of the
volume of a single container or, if there are multiple containers, the
LARGER of either 150% of the largest container volume or 10% of the
total volume of all the containers.
Dan
---------------------------------
Dan Blunk PhD, REA 831.459.3541 blunk**At_Symbol_Here**ucsc.edu
Environmental Programs Manager
Environmental Health & Safety Office
University of California Santa Cruz
-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of
Larry D. McLouth
Sent: Thursday, April 22, 2004 12:38 PM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: [DCHAS-L] Capacity for Secondary Containment
A number of people have asked what the requirements are for secondary
containment at SAAs. I have not found a specific "requirement".
A guideline I've heard is that secondary containment capacity should be
110% of the largest container or 10% of the aggregate volume of all
containers.
What do you use at your facilities?
Any thoughts or comments?
Thanks
Larry