Safety Emporium eyewashes
Safety Emporium eyewashes

Interactive Learning Paradigms, Incorporated

DCHAS-L Discussion List Archive

About This Archive  |   DCHAS-L 2019 Index   |   DCHAS-L Yearly Index   |   DCHAS-L Home Page

About This Archive

DCHAS-L 2019 Index

DCHAS-L Yearly Index

DCHAS-L Home Page


Previous by Date

Subject: Re: [DCHAS-L] possible conversion of under-hood acid cabinet to flammables?

Date: Oct 10, 2019 12:41 UTC

Author: Richard Palluzi <000006c59248530b-dmarc-request**At_Symbol_Here**LISTS.PRINCETON.EDU>

Next by Date

Subject: Re: [DCHAS-L] is drying chromatography media in open cans ok?

Date: Oct 10, 2019 14:04 UTC

Author: TILAK CHANDRA <0000058f112ac338-dmarc-request**At_Symbol_Here**LISTS.PRINCETON.EDU>

Thread context

From: Harry J. Elston <harry**At_Symbol_Here**MIDWESTCHEMSAFETY.COM>

Subject: Re: [DCHAS-L] possible conversion of under-hood acid cabinet to flammables?

Date: Oct 10, 2019 13:19 UTC

Reply-To: ACS Division of Chemical Health and Safety

In-Reply-To: Re: [DCHAS-L] possible conversion of under-hood acid cabinet to flammables?

Demystify: 

To follow up on Richard's note, most knowledgeable AHJs that I've run into frown heavily on venting flammable storage cabinets. I've been able to get an AHJ variance twice, and both times involved thiols/mercaptans in storage and I argued from an exposure perspective, and in both cases we had to severely limit the total quantity of material in the cabinet.

Harry



On Thu, Oct 10, 2019 at 7:48 AM Richard Palluzi <000006c59248530b-dmarc-request**At_Symbol_Here**lists.princeton.edu> wrote:

It is critical to recognize that when you vent a flammable storage cabinet, unless you provide a fire actuated damper on the inlet and outlet you lose all the fire resistance of the cabinet. No flammable storage cabinet vendor I have ever contacted was willing to provide any data to support that a ventilated cabinet passes the required fire testing. All were very clear that they felt the cabinet would fail quickly. Fire rated dampers are available (although h not cheap) but flitting them on under hood cabinets is problematical at best although easily done on standalone cabinets. An example of one can be found at http://www.safetyemporium.com/j-25777.

For more information on this area you may want to look at" Should You Vent a Flammable Storage Cabinet? At https://www.linkedin.com/pulse/should-you-vent-flammable-storage-cabinet-richard-palluzi/.

Note that NFPA 30 The Flammable and Combustible Liquids code, NFPA 45 Fire Protection for Laboratories, and most fire codes prohibit this practice unless adequate mitigative measures are in place.

And certainly you cannot use an acid storage cabinet for a flammable liquid storage cabinet. While they may, in some cases, be made almost identical, the acid storage cabinet is not approved by the manufacturer, not marked properly, and not allowed by any code.

Richard Palluzi

PE, CSP

Pilot plant and laboratory consulting, safety, design,reviews, and training

www.linkedin.com/in/richardppalluzillc/

Richard P Palluzi LLC

72 Summit Drive

Basking Ridge, NJ 07920

rpalluzi**At_Symbol_Here**verizon.net