Subject: Re: [DCHAS-L] CSB Issues New Safety Alert Focused on the Emergency Discharges from Pressure Release Valves

Date: Mar 8, 2023 18:00 UTC

Reply-To: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**Princeton.EDU>

Message-ID: <8221c575-1222-4d3a-bee5-267f033bb7fe**At_Symbol_Here**email.android.com>

In-Reply-To: <4FEB48EB-71DE-4692-A430-4A03A390E84A**At_Symbol_Here**pm.me>

Demystify: 
There have been at least two fires I know of due to a relief device in a lab scale reactor opening and blowing the contents outside the hood because the tygon tubing on the outlet blews off or failed during the relief event so I completely support the concern.

On Mar 8, 2023 11:50 PM, Daniel Kuespert <000015c5a28e7459-dmarc-request**At_Symbol_Here**LISTS.PRINCETON.EDU> wrote:
The CSB is addressing industrial uses, but this is actually a lab issue as well, since I’ve seen people mount reliefs (particularly the angle-pattern type) on pressurized equipment like hydrogenators and point the discharge right at themselves. At minimum, relief discharge needs to go to a hood exhaust if the system contents are hazardous, and if it’s high flow or pressure someone needs to make sure they won't burst the exhaust or overload it and back up into the lab. If the hood exhaust can’t handle the flow, then some kind of alternate arrangement needs to be made—venting it outside and in some cases, the fire code will require a treatment system.

The worst case of this I ever saw was at a cheese plant in New York. I was inspecting the ammonia refrigerant fill point outside, and went to look where it fed. It fed into a receiver vessel, not surprisingly, and I followed the relief line for the vessel to see where it discharged. It went out through the side wall of the machinery room and turned DOWNWARD right above the fill point. I understand that one needs to keep rain out of the discharge line, but any technician who overfilled the receiver vessel would get an anhydrous ammonia shower. I’ve got autopsy photos somewhere of a worker killed by exposure to liquid anhydrous ammonia—quite grim.

I haven’t had a chance to read the safety alert itself—is it readily transferable to lab situations?

Regards,
Dan

-------------------------------------------------
Daniel Kuespert, PhD, CSP
Member, American Chemical Society (ACS)
Member, ACS Division of Chemical Health & Safety (CHAS)
Chair, CHAS 2023
Member, ACS Committee on Chemical Safety, 2023-2025
CHAS Fellow

11101 Wood Elves Way
Columbia, MD 21044-1003
410-992-9709 vox
443-980-0989 mobile
dkuespert@pm.me (personal)


On Mar 7, 2023, at 08:06, Ralph Stuart <ralph@rstuartcih.org> wrote:

To view this message in a browser, please click here

CSB - U.S. CHEMICAL SAFETY BOARD -- An independent federal agency investigating chemical accidents to protect workers, the public, and the environment

CSB Issues New Safety Alert Focused on the Protentional Hazards of Emergency Discharges from Pressure Release Valves

Washington, D.C. March 6, 2023 - Today, the U.S. Chemical Safety and Hazard Investigation Board (CSB) issued a new Safety Alert titled “Hazards Posed by Discharges from Emergency Pressure-Relief Systems.” The CSB’s alert highlights hazards identified with emergency pressure-relief systems from four CSB investigations.  The alert advises facilities that while a discharge from emergency pressure-relief systems can help protect equipment from unexpected and undesired high-pressure events, it can also seriously harm or fatally injure workers and cause extensive damage to a facility if the discharge is not made to a safe location.

CSB Chairperson Steve Owens said, “All four of the incidents highlighted in the CSB’s safety alert underscore the importance of thoroughly evaluating emergency pressure-relief systems to ensure they discharge to a safe location where they will not harm people."

The four incidents highlighted in the CSB’s safety alert resulted in 19 deaths and 207 injuries. They include:

  • On May 19, 2018, an ethylene release ignited, injuring 23 workers at the Kuraray America, Inc. ethylene and vinyl alcohol copolymer plant in Pasadena, Texas. The CSB’s animation of this event shows how this incident occurred during the startup of a chemical reactor system following a turnaround. High-pressure conditions developed inside the reactor and activated the reactor’s emergency pressure relief system, discharging flammable ethylene vapor horizontally into the ambient air in an area where a number of contractors were working.
  • On November 15, 2014, approximately 24,000 pounds of highly toxic methyl mercaptan were released from an insecticide production unit at the E.I. du Pont de Nemours and Company (DuPont) chemical manufacturing facility in La Porte, Texas. The release fatally injured three operators and a shift supervisor inside a manufacturing building. During the early phases of the investigation, CSB investigators identified a number of worker safety issues—separate from the release scenario— including that several emergency pressure-relief systems at the facility were designed to discharge hazardous materials in a way that posed a risk to workers and the public.
  • On May 4, 2009, highly flammable vapor released from a waste recycling process, ignited, and violently exploded at Veolia ES Technical Solutions, LLC, in West Carrollton, Ohio. The incident injured four employees, two seriously.  Following the initial explosion, multiple other explosions occurred that t significantly damaged every structure on the site. Residences and businesses in the surrounding community also sustained considerable damage. The CSB concluded that uncontrolled venting from emergency pressure-relief valves to the atmosphere allowed tetrahydrofuran (THF) vapors to accumulate to explosive concentrations outside process equipment, and the vapors subsequently found an ignition source.
  • On March 23, 2005, during the startup of an isomerization unit following a maintenance turnaround, a series of explosions occurred at the BP refinery in Texas City, Texas. The incident fatally injured 15 workers and injured an additional 180 workers. During the startup, a distillation tower flooded with flammable hydrocarbons and was over-pressurized.  This activated the tower’s emergency pressure-relief system, which created a geyser-like release from the vent stack and formed a flammable vapor cloud that soon ignited and exploded.
CSB Board Member Catherine Sandoval said, “OSHA requires employers to provide a safe workplace. Effective and safe pressure relief systems help ensure safe operations of plants across the country.”

Using findings from these four incidents the CSB’s safety alert issues three key lessons for facilities.
  1. Follow existing good practice guidance.
  2. Evaluate whether the atmosphere is the appropriate discharge location or if there are safer alternatives.
  3. Ensure hazardous chemicals vented into the atmosphere discharge to a safe location.

The alert also calls on companies to evaluate and, when appropriate, update their emergency pressure relief systems to prevent future incidents and protect workers and surrounding communities from harm.
Board Member Sylvia Johnson said, “Our safety alert calls on companies to evaluate and, when appropriate, update their emergency pressure relief systems to prevent future incidents and protect workers and surrounding communities from harm.”

The CSB’s core mission activities include conducting incident investigations; formulating preventive or mitigative recommendations based on investigation findings and advocating for their implementation; issuing reports containing the findings, conclusions, and recommendations arising from incident investigations; and conducting studies on chemical hazards.

The agency's board members are appointed by the president and subject to Senate confirmation. The Board does not issue citations or fines but makes safety recommendations to companies, industry organizations, labor groups, and regulatory agencies such as OSHA and EPA.

Please visit our website, www.csb.gov. For more information, contact Communications Manager Hillary Cohen at Hillary.Cohen@csb.gov.




--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership@dchas.org

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership@dchas.org

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org

Previous post  |  Top of Page  |  Next post