From: Tyrell Towle <tyrelltowle**At_Symbol_Here**GMAIL.COM>
Subject: Re: [DCHAS-L] Emergency Shower and Eyewash Temperatures
Date: Fri, 6 Jul 2018 12:23:45 -0600
Reply-To: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**PRINCETON.EDU>
Message-ID: CAH2MDUM48FHTk4o_EmYgpDOM4N+6nw17W0oEckP_k4nx7EJ7uw**At_Symbol_Here**mail.gmail.com
In-Reply-To <7BAE6125-2D40-46D8-B273-0BB6C7A19EEB**At_Symbol_Here**smu.edu>


Thank you for your input, everyone! This is a lot of great information for me to use moving forward.

Upon further inspection of our setup, there is a single mixing valve beneath each handwashing sink that feeds both the sink and the emergency eyewash. Has anyone encountered this configuration before? To me, it seems that there should be a separate mixing valve for the handwashing sink and the eyewash since they have different temperature requirements.

Anyway, thank you, again!

-Tyrell

On Fri, Jul 6, 2018 at 11:56 AM, Chance, Brandon <bchance**At_Symbol_Here**mail.smu.edu> wrote:
Also, remember that mixing valves fail. I have had situations where mixing valves that served all of the units on a floor have failed on the hot side, resulting in a complete system having water above 120F. We have asked our Facilities group to ensure the valves are part of the building preventative maintenance plan after we had to rebuild or replace a number of them.


Regards,

Brandon S. Chance, MS, CCHO
Director of Environmental Health and Safety
Sustainability Committee Chair
Office of Risk Management
Southern Methodist University
PO Box 750231 | Dallas, TX 75275-0231
T) 214.768.2430 | M) 469-978-8664

"=E2=80=A6 our job in safety is to make the task happen, SAFELY; not to interfere with the work-" Neal Langerman


From: ACS Division of Chemical Health and Safety on behalf of Penny Manisco
Reply-To: ACS Division of Chemical Health and Safety
Date: Thursday, July 5, 2018 at 6:14 PM
To: "DCHAS-L**At_Symbol_Here**PRINCETON.EDU"
Subject: Re: [DCHAS-L] Emergency Shower and Eyewash Temperatures

Hi All,

This is so weird because this exact thing happened in one of our newly renovated labs. A few weeks ago I was instructing students on flushing eyewash and safety shower and noticed the shower was scalding hot. The eyewash/shower had been installed last summer and has been fine all year. I checked a second system in that lab only to find that the shower was not functioning at all. It turned out that someone (contractors remodeling a restroom perhaps?) had erroneously turned off the cold water valve that feeds the emergency equipment. That caused scalding water at one end of the room, and no pressure at the other. The eyewash and shower are fed with water from a mixing valve.

This is why we check!

Best,

Penny Manisco
Chemical Hygiene Officer
Harvey Mudd College

On Thu, Jul 5, 2018 at 2:14 PM, Tyrell Towle <Tyrell**At_Symbol_Here**medpharmholdings.com> wrote:

Hello everyone,

This may seem like a basic question, but I am getting some pushback from our plumbing contractors on this.

We have a brand new facility and I went through to test all of the eyewash and emergency shower stations. At first everything seemed to be working fine, but then I noticed that the emergency eyewash water was getting warmer. I was horrified when the eyewash water became hot. I have never encountered hot eyewash water before. I had the contractors re-plumb the eyewash stations into cold tap water only. Now they are pushing back, wanting to hook the eyewash stations back into the hot water.

I also noticed that our emergency shower is releasing hot water.

Are there any regulations surrounding eyewash and emergency shower temperatures? My understanding has always been to have cold, potable tap water running into emergency showers and eyewashes so that chemical reactions are not accelerated upon exposure to heat. Regardless, with the temperatures that our eyewash stations were reaching, there was no way that anyone could keep their eyeballs open for 10 minutes in this water. Any information is appreciated, especially information that will put this debate to rest.

Thank you!

Tyrell R. Towle, Ph.D.
Senior Chemist
MedPharm Holdings, LLC
www.medpharmholdings.com

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas



--
Penny Manisco,
Chemical Hygiene Officer
Harvey Mudd College

(909)6074217
--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas
--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.